Universal two-channel device RP2-M

Recommended

7050 

The universal two-channel device RP2-M combines all the functions of the RP2-U and RP2-T modifications, and also has the function of data logging (recording to a microSD card).

UNIVERSAL TWO-CHANNEL DEVICE
RP2-M

dev0

Universal two-channel device RP2-M designed to control technological processes that require automatic counting of time intervals (time relay, universal timer), counting the number of incoming pulses, weather-dependent regulation, control of discrete and analog valves, work according to a given program with a time delay; measuring, recording and regulating the temperature of heat carriers and various media in drying ovens, ovens for various purposes and other technological equipment, as well as for measuring other physical parameters and generating an alarm signal. The universal regulator allows you to implement: PID regulator, meter-regulator, regulator with timer, three-position regulator: damper / damper control regulator, weather-dependent regulator.

RS-485 Modbus USB Alarm out

Inputs Timer Class 0.15

 

DISPLAY INFORMATION

dev0

 

 

The controller uses a high-tech LED-display of individual design, providing the user with clear and intuitive information. This display is characterized by a wide viewing angle, the readings on it are perfectly visible even at a great distance, in any lighting conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIVERSALITY

dev0

 

 

Possibility of connecting resistance thermocouples, thermoelectric converters, sensors with a unified output signal of current and voltage. The device has two analog outputs that are configured for the output signal of the desired range, as well as two digital outputs and an alarm output.

 

 

 

 

 

 

 

 

 

 

 

ADAPTIVE PID REGULATOR

PID controller

 

 

In the universal two-channel controller with timer RP2-U, an improved self-tuning algorithm of the PID controller is implemented with the ability to adjust the coefficients during its operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESIGN

dev0

 

 

The universal two-channel regulator with timer RP2-U has an updated housing with terminal connections that allows convenient connection of input sensors and output devices, and also guarantees reliable fastening in a switchboard.
The body is made of flame retardant polycarbonate.

 

 

 

 

 

 

 

 

 

 

 

 

 

CERTIFICATION

device RP2-M meets the requirements of the relevant technical regulations:

  • Technical regulations on electromagnetic compatibility of equipmentapproved by the Resolution of the Cabinet of Ministers of Ukraine dated December 16, 2015 No. 1077 (Official Gazette of Ukraine, 2016, No. 2, Article 72).
  • Technical regulations for low-voltage electrical equipmentapproved by the Resolution of the Cabinet of Ministers of Ukraine dated December 16, 2015 No. 1067 (Official Gazette of Ukraine, 2015, No. 102, Article 3526).

The device complies with the requirements of the relevant standards from the list of national standards that have been applied:

  • DSTU EN 61326-1: 2016, EN 55011: 2016 / A1: 2017 / A11: 2020 - Electrical equipment for measurement, control and laboratory use. Requirements for electromagnetic compatibility;
  • DSTU EN 61010-1: 2014 - Safety requirements for instrumentation and laboratory electrical equipment; DSTU EN 62479: 2015 - Compliance assessment of low-power electronic and electrical equipment with basic limit levels associated with human exposure to electromagnetic fields;
  • DSTU EN 60529: 2014 - Degrees of protection provided by enclosures (IP54).

In addition to the procedure "internal control of production" (module A), which was applied by the manufacturer, the involved accredited conformity assessment body: State Enterprise "All-Ukrainian State Scientific and Production Center for Standardization, Metrology, Certification and Consumer Protection" (SE "Ukrmetrteststandard") performed work on voluntary certification of products and issued a certificate of conformity: No. UA.001.30.01054-21 from 30.09.2021

The RP2-M device complies with standards/normative documents and EU Directives: 2014/30/EU (EMC), 2014/35/EU (LVD), 2014/53/EU (RED), 2011/65/EU (RoHS).

 

               

 

OPERATING MODES RP2-M:

  • Meter;
  • Meter with alarm;
  • Two-position regulator;
  • Two-position regulator with timer;
  • Three-position regulator;
  • Three-position regulator with timer;
  • Discrete PID controller;
  • Discrete PID controller with timer;
  • Analog PID controller;
  • Analog PID controller with timer;
  • works as a PID regulator for valve control;
  • PID controller for gate valve control with timer;
  • also PID controller in the heater / refrigerator system;
  • Weather-dependent regulator;
  • Converter of an input value into an analog signal;
  • Manual dial for analog signal;
  • Direct and reverse counting of impulses;
  • Working with an encoder;
  • Flow meter;
  • Frequency meter;
  • Tachometer;
  • Dispenser;
  • Equipment operating hours counter;
  • Universal timer;
  • Time relay;
  • I / O extension unit.

 

TECHNICAL CHARACTERISTICS RP2-M:

Food

  • 110 - 240 VAC, 50/60 Hz;
  • 12 - 24 VDC.

Internal power supply

  • 24 VDC, load capacity 60 mA.

Interfaces

  • RS-485 (ModBus RTU protocol);
  • isolated RS-485 (ModBus RTU protocol)

Discrete outputs (2 outputs)

  • electromechanical relay (5A, 220 VAC);
  • transistor optocoupler (100 mA, 60 VDC);
  • triac optocoupler (100 mA, 220 VAC).

Discrete inputs (2 inputs)

  • START / STOP / PAUSE timer / block output devices.

Universal inputs (2 inputs)

  • resistance thermocouples;
  • thermoelectric converters;
  • sensors with a unified current output signal (0 ... 5 mA, 0 ... 20 mA, 4 ... 20 mA);
  • sensors with a unified voltage output signal (0 ... 1 V, 0 ... 5 V, 0 ... 10 V).

Alarm output

  • transistor switch (100 mA, at 60 VDC).

Analog outputs (2 outputs)

  • 0… 5 mA, 0… 20 mA, 4… 20 mA (the type of output signal is user-configurable).

FEATURES RP2-M

  • Algorithm of adaptive self-tuning of the PID regulator with improved characteristics of the accuracy of tuning the coefficients and a quick exit to the setpoint;
  • The measurement error is 0.25% of the input value measurement range, excluding the input sensor error;
  • Protection of parameters from unauthorized access.
  • Two independent control channels with time delay;
  • Timer operation with and without slope in one cycle;
  • Programming 10 timer programs and selecting one of the preset timer operating modes without a password;
  • Setting the alarm output operation in steps (ON / OFF) in a cycle;
  • Pulse counter operating frequency up to 20 kHz;
  • Protection of parameters from unauthorized access.
  • Saving the current operating modes in the nonvolatile memory of the device when the power is turned off;
  • Possibility of setting and simultaneous operation of up to 70 universal timer programs;
  • operation of the universal timer by priorities (month, week, day of the week, day, hour, minute, second);
  • Operation of the universal timer for sunrise / sunset;
  • Possibility of setting up to 20 holidays and weekends, on which the universal timer does not execute the configured work programs;
  • Configurable up to 20 steps for time relay;
  • Output control via RS-485 interface;
  • Logger function (data recording to microSD card up to 32GB);
  • Convenient menu navigation;
  • Informative multifunctional indicator;
  • Practical body.

Universal regulator RP2-M  replaces a number of devicespreviously produced by REGMIK:

  • Meters: I1, I2, I2-01;
  • Two-position meter-regulators: RD1, RD2;
  • PID controllers: discrete and analog RP1, RP2;
  • PID regulators for gate valve control: RP1-Z, RP2-Z;
  • Weather-dependent regulator;
  • Regulators with time delay: RD1-T, RD2-T, RP1-T.
  • Universal timers: UT-1, UT-2;
  • Time relay: PB1, PB2;
  • Impulse counters: SI1, SI2, SI1m.

The device can be executed in DIN rail housing RP2-M.

Universal two-channel pulse counter / time relay RP2-T.

Universal two-channel meter / regulator RP2-U.

When designing an RS-485 network, please read the article pdf Button Proper RS-485 network.

Modifications

List of conditional abbreviations:
OK - optotransistor
OS - optosimistor
AC - analog current
P - electromagnetic relay

Information about modifications of the universal two-channel device RP2-M-x1x2x3, Where:

x1 – output types:

0. - 2OC, 2AC;
1. - 2P, 2AC;
2. - 2OK, 2AC;
3. - 2OC;
4. - 2P;
5. - 2OK;
6. - without exits.

x2  – interfaces and power supply of volatile memory:

0. - isolated RS-485 (ModBus RTU protocol) and the presence of a battery for supplying volatile memory;
1. - RS-485 (ModBus RTU protocol) and the presence of a volatile memory battery.

x3 - type instrument power supply:

0.- from the AC network with a nominal value of 110-240 V AC;
1. - from a DC voltage source with a nominal value of 12 ... 24 V DC.

Download

 Настанова з експлуатації та паспорт РП2-М (Редакція 1.6)

 Software available registers of RP2 device

 Test report EN61010 (anl.)

 Test report EN61010 (Ukrainian)

 Certificate of conformity

 Declaration of conformity (Ukrainian)

 CE conformity certificate

Відгуки

Відгуків немає, поки що.

Send review
REGMIK, NVF, PP
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.