PID controller eight-channel RP8

6750 

The eight-channel PID controller RP8 with discrete outputs is designed to regulate the input physical quantities according to the PID law in eight channels. During operation, the device regulates the input value through eight channels using output devices that are connected through the outputs: P, OK, OS.

Description

The eight-channel PID controller RP8 with discrete outputs regulates the input physical quantity according to the proportional-integral-differential (PID) law in eight channels. RP8 works in tandem with an output expansion unit BR8 (sensors are connected to the RP8 device and it transmits control signals of output devices to BR8 via RS-485).

PID controllers with discrete control are used to accurately control the input value using contactless actuators (triacs, thyristors, solid-state relays).

RP8 allows you to perform the following functions

  • measurement of parameters of various objects using standard sensors (resistance thermocouples (temperature sensors) ТСМ (50М, 100М) and ТСП (50П, 100П, Pt100), thermocouples (ТХК, ТХА, ТЖК, etc.), sensors with a unified output current signal and voltage) on eight channels;
  • display on the built-in LED digital indicators of the current and specified parameter values;
  • regulation of a physical quantity according to a proportional-integral-differential (PID) law on eight channels;
  • light indication of the device operating mode;
  • the ability to change the set value (setpoint) for the PID controller;
  • data exchange with a personal computer via RS-485 interface;
  • signal generation "Error";
  • program change of parameters of the transformation characteristics.

Manufacturing modifications:
-panel execution;
- power supply from the 220V alternating voltage network and from the 12..24V constant voltage source;
-types of input signals TC, PT, AN and AT;
-types of output devices P, OK, OS;
- two RS-485 interfaces (for controlling the BR8 and for exchanging data with a personal computer).

Additional Information

Number of channels

Input sensor types

, , , ,

Number of outputs

Output device types

RS-485 interface

Supply voltage, V

,

Characteristics

Input device types
Input primary converter
Measurement range, ° С
Modification
Sensor code
Type
NSH
TS according to DSTU 2858-94
01
TCM 50 W = 1.4260
50M
-50..+200
02
TCM 50 W = 1.4280
50M
-50..+200
03
TSP 50 W = 1.3850
Pt50
-50..+600
04
TSP 50 W = 1.3910
50P
-50..+600
05
TCM 100 W = 1.4260
100M
-50..+200
06
TCM 100 W = 1.4280
100M
-50..+200
07
TSP 100 W = 1.3850
Pt100
-50..+600
08
TSP 100 W = 1.3910
100P
-50..+600
09
TSP 46 W = 1.3910
group 21
-50..+600
71
TSP 500 W = 1.3850
Pt500
-50..+600
72
TSP 1000 W = 1.3850
Pt1000
-50..+600
TS according to DSTU 2837-94
10
THK
L
-30..+600
11
TXA
K
-50..+1200
12
TJK
J
-30..+850
13
CCI 10
S
0..+1750
15
TPR
B
+200..+1800
16
TVR
A-1
0..+2500
AN
21
Voltage АН1 (0-1V)
User defined
22
Voltage AH2 (0-10V)
23
Voltage AH3 (0-5V)
AT
31
AT1 current (0-5 mA)
User defined
32
AT2 current (0-20 mA)
33
AT3 current (4-20 mA)
Output device types
Output device
Load capacity
Electromagnetic relay (P)
5A 220V
Triac optocoupler (OS)
100mA 220V
Transistor optocoupler (OK)
150mA 80V
Power triac (C)
2A 220V
Voltage AH1
0..1V
Voltage AH2
0..10V
Voltage AH3
0..5V
AT1 current
0..5mA
AT2 current
0..20mA
AT3 current
4.20mA
Main technical characteristics of the temperature controller
Description of characteristics
Value
Rated supply voltage, V
220AC
12..24 DC
Supply voltage tolerance, %
± 10
Power consumption, W
6
Set value (setpoint), ° С
-50..2500
Hysteresis, ° С
0..1300
Lower limit of the tolerance field, ° С
-50..2500
The upper limit of the tolerance field, ° С
-50..2500
Conversion characteristic shift, ° С
-99,9..999,9
Cold junction temperature correction, ° С
-99,9..99,9
Conversion slope
0,001..9,999
Digital filter
0,1..99,9
Averaging time, number of measurement periods
0..9
Output device activation delay, s
0..255
Delay of turning off the output device, s
0..255

Modifications

Modifications of panel board PID controllers with discrete outputs
Т [N1] [N2] ТС, [N3] ПТ, [N4] АНх, [N5] АТх / [N6] ОК, [N7] Р, [N8] OC-2I-RS-485 - IPx - Щ
RP2 - 2AT / 2OS-2I- RS-485 - IP24 - Shch
RP 2 2AT 2OS 2I RS-485 IP24 U
Device type: RP-PID controller
[N1] - number of measurement / regulation channels
1
2
4
8
Number and types of input sensors:
[N2] - number of vehicles
[N3] - number of PTs
[N4] - number of sensors with AN
(AH1 - from 0 to 1 V;
AH2 - from 0 to 10 V;
AH3 - from 0 to 5 V)
[N5] - number of sensors with AT
(AT1 - from 0 to 5 mA;
AT2 - from 0 to 20 mA;
AT3 - from 4 to 20 mA)
Number and types of output devices:
[N6] - number of OK - collector openings
[N7] - number of P - relay
[N8] - number of OS - optosimistor
Number of indicators:
2I- 2 four-digit seven-segment indicators
PC communication interface:
RS-485
Device power supply type:
IPI- power supply from an alternating voltage network with a nominal value of 90 ... 240V
IP24 - power supply from a constant voltage source with a nominal value of 12..24V
Type of shell:
Shch- panel board

Download

Passport for RP8 8TS_8R

Відгуки

Відгуків немає, поки що.

Send review
REGMIK, NVF, PP
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.