Two-channel PID controller with analog outputs RP2

Price on request

DISCONTINUED FROM PRODUCTION !!!

Replacement - RP2-U

The RP2 temperature meter-regulator is designed for multistage monitoring and control of temperature conditions of various technological processes in the production of meat and sausage products, in the bakery industry, in incubators, heat chambers, etc.

The RP2 device is designed to receive and convert signals from resistance thermocouples (RT), thermoelectric converters (PT) and sensors with a unified output signal of current (AT) and voltage (AN) into temperature values (or other physical quantities) and display them on built-in digital indicators with simultaneous control of the temperature of objects according to the proportional-integral-derivative (PID) law with a time delay.

RP2 can be used to control the performance of various technological processes in industry, agriculture and utilities (in processes where regulation is required). For example: in autoclaves, sterilizers, for controlling electric valves, etc.

The device automatically controls the state of the sensors, the finding of the measured temperature in the set measurement range.

Main functions of RP2:

  • measurement of temperature, humidity, pressure (or other physical parameters)
    different objects on one or two channels using standard sensors:
    resistance thermoconverters [TC], thermoelectric converters [PT],
    sensors with a unified current output signal 0..5 mA, 0 (4) .. 20 mA [AT] and
    voltage 0..1V, 0..10V [AN];
  • moisture measurement based on the psychrometric method using standard vehicles;
  • display on the built-in LED digital indicators of the current and set
    temperature values in one of the channels;
  • simultaneous display on built-in LED digital indicators
    current temperature values in two channels;
  • regulation of temperature (humidity) of objects according to proportional-integral
    differential (PID) law on two channels;
  • the ability to change the set temperature values (setpoints) for the PID controller by
    two channels;
  • the ability to automatically adjust the coefficients of the PID controller;
  • data exchange with a personal computer via RS-485 interface;
  • light indication of the Operation mode of the Device, generation of the “Error” signal
Number of channels

Input sensor types

, , , ,

Number of outputs

Output device types

, , , , ,

Number of indicators

RS-485 interface

,

Supply voltage, V

,

Characteristics

Input device types
Input primary converter
Measurement range, ° С
Modification
Sensor code
Type
NSH
TS according to DSTU 2858-94
01
TCM 50 W = 1.4260
50M
-50..+200
02
TCM 50 W = 1.4280
50M
-50..+200
03
TSP 50 W = 1.3850
Pt50
-50..+600
04
TSP 50 W = 1.3910
50P
-50..+600
05
TCM 100 W = 1.4260
100M
-50..+200
06
TCM 100 W = 1.4280
100M
-50..+200
07
TSP 100 W = 1.3850
Pt100
-50..+600
08
TSP 100 W = 1.3910
100P
-50..+600
09
TSP 46 W = 1.3910
group 21
-50..+600
71
TSP 500 W = 1.3850
Pt500
-50..+600
72
TSP 1000 W = 1.3850
Pt1000
-50..+600
TS according to DSTU 2837-94
10
THK
L
-30..+600
11
TXA
K
-50..+1200
12
TJK
J
-30..+850
13
CCI 10
S
0..+1750
15
TPR
B
+200..+1800
16
TVR
A-1
0..+2500
AN
21
Voltage АН1 (0-1V)
User defined
22
Voltage AH2 (0-10V)
23
Voltage AH3 (0-5V)
AT
31
AT1 current (0-5 mA)
User defined
32
AT2 current (0-20 mA)
33
AT3 current (4-20 mA)
Output device types
Output device
Load capacity
Electromagnetic relay (P)
5A 220V
Triac optocoupler (OS)
100mA 220V
Transistor optocoupler (OK)
150mA 80V
Power triac (C)
2A 220V
Voltage AH1
0..1V
Voltage AH2
0..10V
Voltage AH3
0..5V
AT1 current
0..5mA
AT2 current
0..20mA
AT3 current
4.20mA
Main technical characteristics of the temperature controller
Description of characteristics
Value
Rated supply voltage, V
220AC
12..24 DC
Supply voltage tolerance, %
± 10
Power consumption, W
6
Set value (setpoint), ° С
-50..2500
Hysteresis, ° С
0..1300
Lower limit of the tolerance field, ° С
-50..2500
The upper limit of the tolerance field, ° С
-50..2500
Conversion characteristic shift, ° С
-99,9..999,9
Cold junction temperature correction, ° С
-99,9..99,9
Conversion slope
0,001..9,999
Digital filter
0,1..99,9
Averaging time, number of measurement periods
0..9
Output device activation delay, s
0..255
Delay of turning off the output device, s
0..255

Modifications

Modifications of PID regulators with analog outputs
Т [N1] [N2] ТС, [N3] ПТ, [N4] АНх, [N5] АТх / [N6] АНх, [N7] АТх -2И-RS-485 - IPх– Щ
RP1 - 1TS / 1AN2-2I- RS-485 - IPI - Shch

 

RP 1 1TS 1АН2 2I RS-485 IPI U
Device type:
RP-PID controller
[N1] - number of measurement / regulation channels
1
2
Number and types of input sensors:
[N2] - number of vehicles
[N3] - number of PTs
[N4] - number of sensors with AN
(AH1 - from 0 to 1 V;
AH2 - from 0 to 10 V;
AH3 - from 0 to 5 V)
[N5] -number of sensors with AT
(AT1 - from 0 to 5 mA;
AT2 - from 0 to 20 mA;
AT3 - from 4 to 20 mA)
Number and types of output devices:
[N6] - number of voltage outputs АН
(AH1 - from 0 to 1 V;
AH2 - from 0 to 10 V;
AH3 - from 0 to 5 V)
[N7] - number of AT current outputs
(AT1 - from 0 to 5 mA;
AT2 - from 0 to 20 mA;
AT3 - from 4 to 20 mA)
Number of indicators:
2I- 2 four-digit seven-segment indicators
PC communication interface:
RS-485
Device power supply type:
IPI- power supply from an alternating voltage network with a nominal value of 90 ... 240V
IP24 - power supply from a constant voltage source with a nominal value of 12..24V
Type of shell:
Shch- panel board

Download

Passport for the regulator RP1_RP2 analog_control_Shch

Відгуки

Відгуків немає, поки що.

Send review
REGMIK, NVF, PP
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.